Solis MV Station

Solis
SKU:
Solis-6300-MV
Availability:
4-6 weeks

Contact us for pricing

Log in for pricing

Weight:
22,600.00 KGS
Width:
626.00 (cm)
Height:
300.00 (cm)
Depth:
253.00 (cm)
Current Stock:

DOWNLOAD DATASHEET

Solis MV Station For 1500 V string inverter Solis 255K

Features:

  • Mainstream 6.3MW subarray, widely used globally
  • 20 foot standard container delivery, easy to transport
  • A complete solution, from inverter to main step-up transformer
  • When the container is lifted to the foundation, only LV and MV cables need to be connected
  • LV panel, transformer and RMU to be placed independently
  • Adopt international first-line brand equipment with reliable quality
  • Full frontal maintenance design
  • Modular design of MV equipment, easy to replace

Datasheet:

Model

6300

LV Panel

MCCB Specification

250 A / 800 Vac / 3P, 14*2 pcs

ACB Specification

3200 A / 800 Vac / 3P, 1*2 pcs

Connection form with transformer

Copper busbar

Transformer

Transformer Type

Oil immersed

Rated Output power

6300 kVA @ 40°C

Max. Output power

6930 kVA @ 40°C 3h

LV/MV Voltage

0.8 kV / 10-35 kV

Max. Input current

2577 A *2

Tapping on HV

±2*2.5%

Vector group

Dy11y11

Frequency

50 Hz / 60 Hz

Cooling type

ONAN

Impedance

7%

Oil Type

Mineral oil (Optional: plant oil)

Winding Material

Al/Al (Optional: Cu/Cu)

Insulation Class

A

Connection form with MV switchgear

Cable

MV Switchgear

Type of insulate

SF6

Rated voltage

12-36 kV

Rated current

630 A

Internal arcing fault

20 kA / 1 s

Qty of Feeder

3 feeders

Protection

LV Surge protection

AC type I+II

AC Input protection

Circuit breaker

Transformer protection

Oil-temperature, oil-level, oil-pressure

Fire protection

Smoke detection, emergency lighting

General Data

Dimensions (W*H*D)

6058*2896*2438 mm

Approximate weight

24 T

Operating temperature range

-25 ~ +60°C

Max. operation altitude

1000 m (standard)

Auxiliary power supply

5 kVA / 230 V (Optional: max. 40 kVA)

UPS

1 kVA 30 min (Optional: max. 2 kVA 2h)

Degree of protection

IP54

Allowable relative humidity range

0-95%

Communication

RS485, Ethernet, Optical fiber

Compliance

IEC 60076, IEC 62271, IEC61439

 

 

single or three-phase:
three-phase
Frequency:
50
MV Rated voltage:
12-36 kV