Solis MV Station
SolisContact us for pricing
Log in for pricing
Solis MV Station For 1500 V string inverter Solis 255K
Features:
- Mainstream 6.3MW subarray, widely used globally
- 20 foot standard container delivery, easy to transport
- A complete solution, from inverter to main step-up transformer
- When the container is lifted to the foundation, only LV and MV cables need to be connected
- LV panel, transformer and RMU to be placed independently
- Adopt international first-line brand equipment with reliable quality
- Full frontal maintenance design
- Modular design of MV equipment, easy to replace
Datasheet:
Model |
6300 |
LV Panel |
|
MCCB Specification |
250 A / 800 Vac / 3P, 14*2 pcs |
ACB Specification |
3200 A / 800 Vac / 3P, 1*2 pcs |
Connection form with transformer |
Copper busbar |
Transformer |
|
Transformer Type |
Oil immersed |
Rated Output power |
6300 kVA @ 40°C |
Max. Output power |
6930 kVA @ 40°C 3h |
LV/MV Voltage |
0.8 kV / 10-35 kV |
Max. Input current |
2577 A *2 |
Tapping on HV |
±2*2.5% |
Vector group |
Dy11y11 |
Frequency |
50 Hz / 60 Hz |
Cooling type |
ONAN |
Impedance |
7% |
Oil Type |
Mineral oil (Optional: plant oil) |
Winding Material |
Al/Al (Optional: Cu/Cu) |
Insulation Class |
A |
Connection form with MV switchgear |
Cable |
MV Switchgear |
|
Type of insulate |
SF6 |
Rated voltage |
12-36 kV |
Rated current |
630 A |
Internal arcing fault |
20 kA / 1 s |
Qty of Feeder |
3 feeders |
Protection |
|
LV Surge protection |
AC type I+II |
AC Input protection |
Circuit breaker |
Transformer protection |
Oil-temperature, oil-level, oil-pressure |
Fire protection |
Smoke detection, emergency lighting |
General Data |
|
Dimensions (W*H*D) |
6058*2896*2438 mm |
Approximate weight |
24 T |
Operating temperature range |
-25 ~ +60°C |
Max. operation altitude |
1000 m (standard) |
Auxiliary power supply |
5 kVA / 230 V (Optional: max. 40 kVA) |
UPS |
1 kVA 30 min (Optional: max. 2 kVA 2h) |
Degree of protection |
IP54 |
Allowable relative humidity range |
0-95% |
Communication |
RS485, Ethernet, Optical fiber |
Compliance |
IEC 60076, IEC 62271, IEC61439 |
- single or three-phase:
- three-phase
- Frequency:
- 50
- MV Rated voltage:
- 12-36 kV