Technical Specification |
SUN2000-12KTL-M5 |
SUN2000-15KTL-M5 |
SUN2000-17KTL-M5 |
SUN2000-20TL-M5 |
SUN2000-25KTL-M5 |
Efficiency |
|||||
Max. efficiency |
98.4% |
||||
European weighted efficiency |
97.9% |
98.0% |
98.1% |
98.1% |
98.2% |
Input |
|||||
Recommended max. PV power 1 |
18,000 Wp |
22,500 Wp |
25,500 Wp |
30,000 Wp |
37,500 Wp |
Max. input voltage 2 |
1100 V |
||||
Full-load MPPT voltage range |
370V~800V |
410V~800V |
440V~800V |
480V~800V |
530V~800V |
MPPT Operating voltage range 3 |
200 V ~ 1000 V |
||||
Start-up voltage |
200 V |
||||
Rated Input voltage |
600 V |
||||
Max. input current per MPPT |
30 A (two string) / 20 A (single string) |
||||
Max. short-circuit current |
40 A |
||||
Number of MPP trackers |
2 |
||||
Max. number of inputs |
4 |
||||
Output |
|||||
Grid connection |
Three phase |
||||
Rated output power |
12,000 W |
15,000 W |
17,000 W |
20,000 W |
25,000 W |
Max. apparent power |
13,200 W |
16,500 W |
18,700 W |
22,000 W |
27,500 W |
Rated output voltage |
220 Vac/ 380 Vac, 230 Vac/ 400 Vac, 239.6 Vac/ 415Vac, 3W + N + PE |
||||
Rated AC Grid Frequency |
50 Hz / 60 Hz |
||||
Max. output current |
18.2A/380Vac |
25.2A/380Vac |
28.6A/380Vac |
33.6A/380Vac |
42.0A/380Vac |
17.3A/400Vac |
23.9A/400Vac |
27.1A/400Vac |
31.9A/400Vac |
39.9A/400Vac |
|
16.7A/415Vac |
23.1A/415Vac |
26.1A/415Vac |
30.8A/415Vac |
38.5A/415Vac |
|
Adjustable power factor |
0.8 leading ... 0.8 lagging |
||||
Max. total harmonic distortion |
≤3 % |
||||
Features & Protections |
|||||
Overvoltage Category |
PV Ⅱ/AC Ⅲ |
||||
Input-side disconnection device |
Yes |
||||
Anti-islanding protection |
Yes |
||||
AC over-current protection |
Yes |
||||
DC reverse-polarity protection |
Yes |
||||
String fault detection |
Yes |
||||
DC surge protection |
TYPE II |
||||
AC surge protection |
CLASS II |
||||
Residual current monitoring unit |
Yes |
||||
Arc fault protection |
Yes |
||||
Ripple control ripple control |
Yes |
||||
Integrated PID recovery 4 |
Yes |
||||
General Data |
|||||
Operation temperature range |
-25 ~ + 60 °C (-13 °F ~ 140 °F) |
||||
Relative humidity |
0 % RH ~ 100% RH |
||||
Max. operating altitude |
0 ~4,000 m (13,123 ft.) (Derating above 2000 m) |
||||
Cooling |
Smart air cooling |
||||
Display |
LED Indicators; Integrated WLAN + FusionSolarApp |
||||
Communication |
RS485; WLAN/Ethernet via Smart Dongle-WLAN-FE (Optional) 4G / 3G / 2G via Smart Dongle-4G (Optional) |
||||
Weight (with mounting plate) |
21kg (46.4 lb) |
||||
Dimensions (W x H x D) (incl. mounting plate) |
546 x 460 x 228mm (21.5 x 18.1 x 9.0 inch) |
||||
Degree of protection |
IP66 |
||||
Optimizer Compatibility |
|||||
DC MBUS compatible optimizer |
SUN2000-450W-P, SUN2000-450W-P2, SUN2000-600W-P, SUN2000-1300W-P, SUN2000-1100W-P |
||||
Standard Compliance (more available upon request) |
|||||
Safety |
EN/IEC 62109-1,EN/IEC62109-2 |
||||
Grid connection standards |
G99,EN50549,CEI0-21,CEI0-16,VDE-AR-N-4105,VDE-AR-N-4110,C10/11,ABNT, VFR2019,UNE 217001, UNE 217002,RD 244, TOR D4,IEC61727,IEC62116 |
- single or three-phase:
- three-phase
- Frequency:
- 50
- Voltage:
- 400