DEYE 80KW Three Phase Hybrid Inverter

DEYE
SKU:
SUN-80K-SG02HP3-EU-EM6
Availability:
4-6 weeks

Contact us for pricing

Log in for pricing

Weight:
112.50 KGS
Width:
75.60 (cm)
Height:
107.70 (cm)
Depth:
46.40 (cm)
Current Stock:

DOWNLOAD DATASHEET

Three Phase Hybrid Inverter

Features:

  • 100% unbalanced output, each phase
  • AC couple to retrofit existing solar system
  • 10 pcs parallel for on-grid and off-grid operation; Support multiple batteries parallel
  • charging/discharging current of 160A
  • High voltage battery, higher efficiency
  • 6 time periods for battery charging/discharging
  • Support storing energy from diesel generator

Technical Specification:

Model

SUN-60K-SG02HP3

-EU-EM6

SUN-75K-SG02HP3

-EU-EM6

SUN-80K-SG02HP3

-EU-EM6

Battery Input Data

Battery Type

Lithium-ion

Battery Voltage Range (V)

160-1000

Max. Charging Current (A)

80+80

Max. Discharging Current (A)

80+80

Charging Strategy for Li-ion Battery

Self-adaption to BMS

Number of Battery Input

2

PV String Input Data

Max. PV Access Power (W)

120000

150000

160000

Max. PV Input Power (W)

96000

120000

128000

Max. PV Input Voltage (V)

1000

Start-up Voltage (V)

180

MPPT Voltage Range (V)

150-850

Rated PV Input Voltage (V)

650

Max. Operating PV Input Current (A)

36+36+36+36+36+36

Max. Input Short-Circuit Current (A)

54+54+54+54+54+54

No. of MPP Trackers/

No. of Strings MPP Tracker

6/2+2+2+2+2+2

AC Input/Output Data

Rated AC Input/Output Active Power (W)

60000

75000

80000

Max. AC Input/Output Apparent Power (VA)

66000

82500

88000

Rated AC Input/Output Current (A)

91/87

113.7/108.7

121.3/115.9

Max. AC Input/Output Current (A)

100/95.7

125/119.6

133.4/127.6

Max. Continuous AC Passthrough (grid to load) (A)

200

Peak Power (off-grid) (W)

1.5 times of rated power, 10s

Power Factor Adjustment Range

0.8 leading to 0.8 lagging

Rated Input/Output Voltage/Range (V)

220/380V, 230/400V 0.85Un-1.1Un

Rated Input/Output Grid Frequency/Range(Hz)

50/45-55, 60/55-65

Grid Connection Form

3L+N+PE

Total Current Harmonic Distortion THDi

<3% (of nominal power)

DC Injection Current

<0.5% In

Efficiency

Max. Efficiency

97.60%

Euro Efficiency

97.0%

MPPT Efficiency

>99%

Equipment Protection

Integrated

DC Polarity Reverse Connection Protection, AC Output Overcurrent Protection, Thermal Protection,

AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring,

Overvoltage Load Drop Protection, Ground Fault Current Monitoring, Arc Fault Circuit Interrupter (optional),

Power Network Monitoring, Island Protection Monitoring, Earth Fault Detection, DC Input Switch,

DC Terminal Insulation Impedance Monitoring, Residual Current (RCD) Detection, Surge protection level

Surge Protection Level

TYPE II(DC), TYPE II(AC)

Interface

Communication Interface

RS485/RS232/CAN

Monitor Mode

GPRS/WIFI/Bluetooth/4G/LAN(optional)

General Data

Operating Temperature Range (℃)

-40 to +60℃, >45℃ Derating

Permissible Ambient Humidity

0-100%

Permissible Altitude

3000m

Noise (dB)

≤65

Ingress Protection(IP) Rating

IP65

Inverter Topology

Non-Isolated

Over Voltage Category

OVC II(DC), OVC III(AC)

Cabinet Size (WxHxD mm)

606×927×314 (Excluding Connectors and Brackets)

Weight (kg)

97.5

Type of Cooling

Intelligent Air Cooling

Warranty

5 Years/10 Years

the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy

Grid Regulation

IEC 61727, IEC 62116, CEI 0-21, EN 50549, NRS 097, RD 140, UNE 217002,

OVE-Richtlinie R25, G99, VDE-AR-N 4105

Safety / EMC Standard

IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2

 

 

7 years
single or three-phase:
three-phase
Frequency:
50
Voltage:
380
Battery Voltage:
160-1000