Choosing Solar Cable and MC4 Connectors: Cross-Section, Voltage, Crimping

4, 6 and 10 mm² solar cable, DC voltage class, UV and temperature resistance, connector compatibility and correct crimping
November 16, 2026 by
Nastech Solar

Short answer: On the DC side, use EN 50618 (H1Z2Z2-K) compliant solar cable of the 1500 V DC class, and choose the cross-section by current-carrying capacity and voltage drop: 4 or 6 mm² for short residential runs, 10 mm² for long runs. For MC4 connectors, choose the model that fits the cable cross-section and outer diameter, make sure the two mating halves are from the same manufacturer and of the same type, and crimp the contacts with the correct crimping tool.

Why solar cable is not ordinary cable

A DC string cable works on the roof for years under sun, rain, high surface temperatures and mechanical stress. That is why cross-linked, halogen-free solar cable with fine-stranded copper conductors is used instead of PVC-insulated building cable. For example, take the HIS HIKRA SOL 6mm² Solar Cable; it complies with EN 50618 (H1Z2Z2-K) and IEC 62930 and has a tinned fine-stranded copper conductor (IEC 60228 Class 5), electron-beam cross-linked polyolefin insulation and an XLPO outer sheath. Key values of the two cross-sections in the catalogue:

PropertyHIKRA SOL 6 mm²HIKRA 10 mm²
Rated voltage1.5 kV DC1.5 kV DC
Max. permitted operating voltage1.8 kV DC1.8 kV DC
Max. conductor resistance3.39 Ω/km1.95 Ω/km
Outer diameter6.0 mm (±0.2 mm)7.1 mm (±0.2 mm)
Ambient temperature-40 °C to +90 °C-40 °C to +90 °C
Max. conductor temperature+120 °C+120 °C
Min. installation temperature-25 °C-25 °C
Min. bending radius (flexible / fixed)10x / 4x cable diameter10x / 4x cable diameter

Cross-section: 4 mm², 6 mm² or 10 mm²?

The cross-section is chosen by two criteria. The first is current-carrying capacity: the string current is calculated from the panel's short-circuit current (Isc) with a safety margin, and the cable's capacity is derated according to the installation method, the ambient temperature and how many cables share the same duct. The second is voltage drop, and in most rooftop projects this is the deciding factor.

Voltage drop is found with a simple calculation: ΔU = I × R × 2L (out and back). Example: the max. resistance of HIKRA SOL 6 mm² cable is 3.39 Ω/km. For a string 50 m from the inverter, the round trip is 100 m, i.e. about 0.34 Ω. At a string current of 13 A, the drop is about 4.4 V and the loss about 57 W; on a 600 V string, that is about 0.7%. With HIKRA 10 mm² cable (1.95 Ω/km), the same run drops to about 2.5 V and 33 W.

A practical approach: on short, low-current runs, 4 mm² may be enough; with modern high-current solar panels and long string runs, 6 mm² is a safer default; on very long runs and combined DC lines, consider 10 mm². When you increase the cross-section, remember to choose the connector accordingly.

DC voltage class: 1000 V or 1500 V?

The voltage class of the cable and connector must be above the open-circuit voltage the string reaches on the coldest day. Panel Voc rises as the temperature falls, so the calculation uses the lowest ambient temperature on site, not the STC value. HIKRA cables have a rated voltage of 1.5 kV DC (max. permitted operating voltage 1.8 kV DC), and Stäubli MC4-Evo 2 connectors have a rated voltage of DC 1500 V (IEC, JET, UL). The same material can therefore be used in both 1000 V and 1500 V systems.

UV, temperature and outdoor conditions

Rooftop cables are exposed to direct sun, and the temperature behind the panels rises noticeably. HIKRA SOL 6 mm² is UV-resistant and has an additional certificate for floating PV (TÜV PV 1500-WR); HIKRA 10 mm² is UV- and weather-resistant and suitable for direct burial. Install at -25 °C or above; at lower temperatures the insulation stiffens and can be damaged when bent.

On the connector side, the MC4-Evo 2 has an ambient temperature range of -40 °C...+85 °C and an upper limit temperature of 115 °C. Its protection rating is IP68 (1 m, 1 h) when mated and only IP2X when unmated. So close unconnected ends with sealing caps, do not leave connectors on the roof surface or where water can collect, fix cables with UV-resistant clips and keep them away from sharp edges.

Connector compatibility: same manufacturer, same type

One of the most common mistakes in the field is mating "MC4 compatible" connectors from different manufacturers. Two connectors that seem to fit may differ in contact geometry, material and tolerances; the result is higher contact resistance, heating, loss of sealing and, in the worst case, arcing and fire. The general installer rule: the two mating halves must be from the same manufacturer and of the same type. Check the connector type at the end of the panel cable and at the inverter input, and fit a connector of the same manufacturer and type on the other side.

Cross-section and outer diameter must also match. The Stäubli MC4-Evo 2 Male Connector, 4-6mm² and its female counterpart are designed for 4 and 6 mm² conductors, with a cable gland diameter range of 6.4–8.4 mm. The 10 mm² versions are for 10 mm² conductors and a gland range of 6.1–7.3 mm; the 7.1 mm outer diameter of HIKRA 10 mm² cable falls within this range. By contrast, the catalogue outer diameter of HIKRA SOL 6 mm² cable is 6.0 mm, below the 6.4–8.4 mm gland range of the 4–6 mm² MC4-Evo 2; confirm with us before ordering which connector version has a suitable gland range for this cable. On every project, compare the cable's outer diameter with the connector's gland range; a cable outside the range compromises sealing. Using red and black cables to avoid mixing up the poles also makes the job easier.

Crimping: the right tool, the right steps

MC4-Evo 2 connectors are crimp connections; the tinned copper contacts and the MULTILAM contact system are designed for a max. contact resistance of 0.2 mΩ. This value is only reached with a crimp made with the correct die and positioner; using general-purpose pliers raises contact resistance and leads to heating over time.

  1. Cut the cable straight and clean.
  2. Strip it to the length given in the assembly instructions; check that no strands are cut.
  3. Crimp the contact that matches the cross-section with the correct positioner.
  4. Push the contact into the housing until it is seated, and check it with a gentle pull.
  5. Tighten the gland to the torque given in the instructions.
  6. Mate the connectors and check that they lock; use only the unlocking tool to separate them.

Stäubli PV Installer Tool Case for MC4 contains the original tools for all of these steps: MC4 and MC4-Evo 2 crimping pliers with positioner, cable stripping pliers, a cable cutter, a torque tool, test plugs, unlocking tools and sealing caps. The case is configured for 4, 6 and 10 mm² open crimp contacts.

Pre-installation checklist

  • Is the cable EN 50618 (H1Z2Z2-K) compliant and of the 1500 V DC class?
  • Was the cross-section chosen by the current and voltage-drop calculation?
  • Is the string Voc on the coldest day below the cable, connector and inverter limits?
  • Do the connector cross-section and gland range match the cable's outer diameter?
  • Are the two mating halves from the same manufacturer and of the same type?
  • Was the crimp made with the manufacturer's tool and checked with a pull test?
  • Are unused ends capped, cables fixed and the bending radius respected?

You can find all solar cables and MC4 connectors in the Cables and Connectors category; for long runs, the HIS HIKRA 10mm² Solar Cable is in this category too.

Frequently Asked Questions

Should I use 4 mm² or 6 mm² solar cable?

Look at the run length and the string current. On short, low-current runs, 4 mm² may be enough; with high-current panels and long runs, 6 mm² reduces voltage drop and heating. Decide with the ΔU = I × R × 2L calculation.

Can MC4 connectors from different brands be mated?

This is not recommended. Two connectors of different brands that physically fit may differ in tolerances and materials, which leads to higher contact resistance, heating and loss of sealing. The two mating halves must be from the same manufacturer and of the same type.

Can 1500 V solar cable be used in a 1000 V system?

Yes. There is no problem as long as the voltage class is above the system voltage. HIKRA cables have a rated voltage of 1.5 kV DC, and MC4-Evo 2 connectors a rated voltage of DC 1500 V.

Can MC4 crimping be done with ordinary pliers?

It should not be. Keeping contact resistance low depends on a crimp made with the correct die and positioner. Use the connector manufacturer's crimping pliers and assembly instructions.

Does an unmated MC4 connector let water in?

The MC4-Evo 2 is protected to IP68 (1 m, 1 h) when mated, but only IP2X when unmated. Close unused ends with sealing caps.


Let's put together the cable cross-section and connector list for your project. Request a quote.